Our lumber products are not listed currently in our on-line catalog. We have an extensive line of lumber products in inventory, please call the store for details. We do not offer shipping at this time. We apologize for any inconvenience.

Southwire 14-19 SD CU THHN-THWN-MTW-AWM UL/c(UL) RED 500 FT

Southwire



Construction

  • Conductor: Solid sizes #14 AWG - #10 AWG use soft drawn bare copper per ASTM B3. Stranded sizes #14 AWG - #10 AWG use a combination-unilay stranded soft drawn bare copper per ASTM B787.
  • Insulation: Heat and moisture resistant PVC
  • Sheath: Nylon


Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Machine Tool Wiring (MTW)
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Federal Specification A-A-59544
  • NMX-J-010-ANCE Thermoplastic insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements


Application & Features


APPLICATION

Southwire THHN copper conductors are primarily used in conduit for branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. These conductors have multiple ratings depending upon the product application.

Allowable temperatures are as follows:

  • THHN or T90 Nylon- Dry locations not to exceed 90°C
  • THWN- Wet locations not to exceed 75°C or dry locations not to exceed 90°C or locations not to exceed 75°C when exposed to oil
  • TWN75- Wet locations not to exceed 75°C
  • MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
  • AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material


FEATURES

  • Gasoline and Oil Resistant II
  • VW-1 Sizes 14 through 10 AWG
  • FT1 All Sizes
  • AWM- Sizes 14 through 10 AWG
  • MTW- Stranded Constructions Only
  • RoHS Compliant